Question 1
A restroom renovation will place 26 drainage fixture units on a 3-inch horizontal fixture branch laid at 1/4 inch per foot. The installer requests approval using the 42-DFU capacity listed for a 3-inch building drain at that slope. The branch receives public water closets and lavatories. How should this sizing submittal be evaluated?
Show answer & explanation
Correct answer: D - Reject: a 3-inch horizontal fixture branch is limited to 20 DFU.